MBQ2Z Automatic Transformer Switch

Application:
MBQ2Z series automatic transfer switch(ATS) is suitable for the transfer between two power sources,common source(power supply Ⅰ) and standby power supply(power supply Ⅱ). Whose rated voltage is below 50Hz,400V(AC) when one power supply malfunctions to assure the safe,and stable power supply.The setting mainly used for hospital,shopping center,bank,and chemical industry,metallurgy,high building,military facilities etc important situation where power breaking can't be allowed.This product complies with standards of IEC60947-6-1,GB14048,11-2002,etc.
Features:
1.Provided with such protective functions as checking two sources of voltage at the same time.protection when any one phase or one phase above experiences under or over-voltage,guide phase.
2.When two sources have abnormal or faulty tripping (overload,short circuit),the controller won't send out the order to realize the protective function of reopening and closing
3.Six working modes:manual control,self-throw self-recover,common source (power supply Ⅰ),standby power supply(power supply Ⅱ),breaking electricity and re-tripping,self-throw no self-recover
4.When the working mode is in the automatic control state,it has two self-throw no slef-recover,self-throw,and self-recover functions:
a.Self-throw non-self recover:when the device enters the working state,power supply Ⅰ automatically throws into supplying electricity;when power supply Ⅰhas an abnormity,it will automatically transfer to power supply Ⅱ;when power supply Ⅰrecovers,it doesn't transfer until power supply Ⅱ has an abnormity,then it will automatically transfer to power supply Ⅰ.
b.Self-throw and self-recover:when the device enters the working state,the common source throws in to supplying electricity;when power supply has an abnormity,it will automatically transfer tostandby power supply;when common power supply recovers,it will automatically recover common power supply;but when the standby power supply has an abnormity,the controller will emit an alarm soured.
Specifications:
| Model | MCCB Applied | No of pole and short circuit breaking capacity | Rated current | Rated ultimate short circuit breaking capacity lcu kA rated insulation voltage | |
| L | M | ||||
| MBQ2Z-63 | MBM1-63 | 3 Pole(L,M),4 Pole | 6, 10, 16, 20, 25, 32, 40, 50, 63 | 25 | 50 |
| MBQ2Z-100 | MBM1-100 | 3 Pole(L,M,H),4 Pole | 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 | 35 | 50 |
| MBQ2Z-160 | MBM1-160 | 3 Pole(L,M,H),4 Pole | 100, 125, 140, 160 | 35 | 65 |
| MBQ2Z-225 | MBM1-225 | 3 Pole(L,M,H),4 Pole | 100, 125, 140, 160, 180, 200, 225 | 35 | 65 |
| MBQ2Z-400 | MBM1-400 | 3 Pole(L,M,H),4 Pole | 225, 250, 315, 350, 400 | 50 | 65 |
| MBQ2Z-630 | MBM1-630 | 3 Pole(L,M,H),4 Pole | 400, 500, 630 | 50 | 65 |
| MBQ2Z-800 | MBM1-800 | 3 Pole(L,M,H),4 Pole | 630, 700, 800 | 50 | 65 |
| MBQ2Z-1250 | MBM1-1250 | 3 Pole(L,M) | 800, 1000, 1250 | 65 | |
Next Page: MBQ2E Automatic Transformer Switch
Keyword: MBQ2Z Automatic Transformer Switch Automatic Transformer Switches