MBQ3 Automatic Transformer Switch

MBQ3 - Automatic Transformer Switch

 

Application:
MBQ3 series automatic transfer switch(A.T.S) suits for the transfer between two powers(Primary power and secondary power),whose rated voltage is beneath 600V(AC),control voltage is under AC220V.It is the new pro duct to replace the conventional one which made up of AC contactor and circuit breaker,and widely used in hospitals,hotels,markerts,post and telecommunications,fire,high building,industrial assembly line,etc.

Features and characteristics:
1.Excitation type electrorriagnteism driving,direct current pulse operation,transfer fast,the coil will not give out heat and cause noise, can save the energy.
2.Two operation modes:power-operated and hand-operated.
3.Having electric interlocker and mechanical interlocker,this can ensure two powers not be electrified at the same time.
4.Big-size contacts have steady and reliable electric conductivity.
5.Good arc extinguishing feature can make the switch be operated even it is in power.
6.Rated insulation voltage:660V;Rated voltage:380V 660V;Time of change over;0.1S

Structure and operation principle:
1.MBQ3 series automatic transfer switch is the real and integral designing switch,but not the conventional combination switch.The switch is made up of main contact system and electric & mechanical interfockers control system which can ensure two powers not be electrified at the same time.The main contacts has,its own arc extinguish chamber.This switch can be transferred by the hand.
2.Excitation type electromagenteism straight-line driving make the switch transfer more reliable and fast,and be aseismatic.When the switch is in transferring,the coil may be electrification(the time is less than 0.1S),and when completes,the coil and other control parts are out of electricity.
3.In normal state,the primary power is working.If the primary power happens to be trouble such as power cut,over voltage,under voltage or phase failure,it automatically change over to the secondary power passed by the automatic controller,when recovering to the normal state,it returns to the primary power agair.Meanwhile,if the secondary power in trouble,the controller will send out alarm to warn people to repair it timely.

Specifications:

Model Rated current(A) Operation current(A) Mechanical life(times) Electrical life(times) Weight(kG) Operation cycle
2P 3P 4P 2P 3P 4P
MBQ3-40N 40 3.5 8000 3000 4 4.5 5.5 20 20 20
MBQ3-63N 63 3.5 8000 3000 4 4.5 5.5 20 20 20
MBQ3-125N 125 3.5 8000 3000 4 4.5 5.5 20 20 20
MBQ3-160T 160 3.5 6000 2000   16 18 20 20 20
MBQ3-200T 200 3.5 6000 2000   17 19 20 20 20
MBQ3-250T 250 3.5 6000 2000   18 20 20 20 20
MBQ3-400T 400 3.5 6000 2000   19 21 20 20 20
MBQ3-630T 630 3.5 6000 2000   20 22 20 20 20
MBQ3-630M 630 16 2500 500   37 42.5 15 15 15
MBQ3-800M 800 16 2500 500   39 46 20 20 20
MBQ3-1000M 1000 16 2500 500   41 48 25 25 25
MBQ3-1250M 1250 16 2500 500   48 57 25 25 25
MBQ3-1600M 1600 16 2500 500   56 67 25 25 25
MBQ3-2000M 2000 16 1500 500   64 85.5 50 50 50
MBQ3-2500M 2500 16 1500 500   79.5 104 50 50 50
MBQ3-3200M 3200 16 1500 500   98 125 100 100 100

 