MBQ5 Automatic Transformer Switch

Summarization:
MBQ5 automatic transfer switch(ATSE) is composed of switch and logic,and without additional controller.The faceplate showed with LCD and the operation be arranged by total English,it achieved the machine and power incorporately.It has the function of voltage text,frequency text,communication interface,fire fighting interface,electric,and inlock,and could achieve automatic,dynamoeletric long-distance,urgently manual control.
Operation been effected by the logic control board with kinds of logic order to manage the operation circulation of electromotor and gear-box.The electromotor drive the switch spring to cumulate the energy and release indtantaneously accelerating machine,connect the breaking circuit or the circuit transformation.It could achieve the safe insulation through obvious and eyeable estate enhance the all items of the electric capability and machine capability.
The whole switch are made of matel crust,cabinet and solid which is below 100A.The switch above of 125A whose crust is made of metal and the switch part adopts glass fibre unsaturalted polyester colophony hull,with strong insulating capability,protecting capability and reliable operating safety capability.
This switch is suitable for the automatic transfer of the main power supply and reverse power supply of the power supply system or the automatic transfer of the two pieces of the loading equipment and the safety insulation.
This switch has the advantage of handsome sculpt,new and compact design,small volumeand full function,it is the perfect choice among the congener products.
MBQ5 series products have passed the test of electromagnetism compatible capability and get the fullwill authentication certification.
According to the standard:
International standard:IEC60947-1(1998)(The first part of the low voltage switch equipment and control equipment:general principles)
State standard:GB/T 14048.1-2002(Low voltage switch equipment and control equipment:general principles)
The circumstance and the prupose for usage:
The circumstance for usage:
The height above sea level is not exceed 2000 meters;
The circumstance temperature is not higher than 40
and not lower than -5
;
The opposite humidity is not bigger than 95%;
The circumstance without any medium of the danger f blast;
The circumstance without any rain and snow affection.
Note:If it used anticipatively under the condition of the circumstance temperature higher than +40
or below thann -5
to -45
,the user should explain it to the manufacturer.
Usage:Altemating current,50Hz,rated voltage 380V,direct current rated voltage 220V,rated current to 1600A.used for noncontinually switch on and breaking circuit.
Electric capability and mechanism capability:
| Rated current(A) | 16A | 20A | 25A | 32A | 40A | 50A | 63A | 80A |
| Rated insulating voltage Ui(V) | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 |
| The strength of insulating power (V) | 3000 | 3000 | 3000 | 3000 | 3000 | 3000 | 3000 | 3000 |
| Rated concussion endurance voltage Uimp kV(The installation sort IV) | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| Rated operating current le(A) | ||||||||
| 380V AC31 AC33 AC35 |
16 16 16 |
20 20 20 |
25 20 25 |
32 25 32 |
40 32 40 |
50 40 50 |
63 40 63 |
80 63 80 |
| 220V DC31 DC33 DC35 |
16 16 16 |
20 20 20 |
25 20 25 |
32 25 32 |
40 32 40 |
50 40 50 |
63 40 63 |
80 63 80 |
| The power of electromotor P(kW) | ||||||||
| 380V | 8 | 10 | 15 | 15 | 20 | 25 | 30 | 30 |
| Overloading capability | ||||||||
| Rated short time endurance current lcw(kA Rms)0.1S/1.0S | 9/5 | 9/5 | 9/5 | 9/5 | 9/5 | 9/5 | 9/5 | 9/5 |
| Switch on breaking capability | ||||||||
| Rated breaking capacity(A Rms)AC33 380V | 125 | 160 | 200 | 250 | 320 | 400 | 500 | 640 |
| Rated switch on capability(A Rms)AC33 380V | 160 | 200 | 250 | 320 | 400 | 500 | 630 | 800 |
| Rated short cicuit switch on capability lcm(kA peak value) | 8 | 8 | 8 | 8 | 8 | 8 | 10 | 10 |
| Mechanism life (circulate times) | 100000 | 100000 | 100000 | 100000 | 100000 | 100000 | 100000 | 100000 |
| Electric life(circulatetimes) | ||||||||
| COSφ=0.65AC33 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 |
| Switch time | ||||||||
| 1-0-11or 11-0-1(s) 1-0 or 11-0(s) |
1.0 0.5 |
1.0 0.5 |
1.0 0.5 |
1.0 0.5 |
1.0 0.5 |
1.0 0.5 |
1.0 0.5 |
1.0 0.5 |
| Electric control consume | ||||||||
| Power supply voltage 24V(DC)(w) 220V(AC)(w) |
25 25 |
25 25 |
25 25 |
25 25 |
25 25 |
25 25 |
25 25 |
25 25 |
| Operating moment(Nm) | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| Weight(Kg)3P | 4.8 | 4.8 | 4.8 | 4.8 | 4.8 | 4.8 | 4.8 | 5.0 |
| Weight(Kg)4P | 5.0 | 5.0 | 5.0 | 5.0 | 5.0 | 5.0 | 5.0 | 5.2 |
| Rated current(A) | 100A | 125A | 160A | 200A | 250A | 400A | 11630A | 1000A | 1250A | 1600A |
| Rated insulating voltage Ui(V) | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 |
| The strength of insulating power (V) | 3000 | 5000 | 5000 | 5000 | 5000 | 8000 | 8000 | 1000 | 10000 | 10000 |
| Rated concussion endurance voltage Uimp kV(The installation sort IV) | 6 | 8 | 8 | 8 | 8 | 12 | 12 | 12 | 12 | 12 |
| Rated operating current le(A) | ||||||||||
| 380V AC31 AC33 AC35 |
100 80 100 |
125 125 125 |
160 160 160 |
200 200 200 |
250 250 250 |
400 340 400 |
630 536 630 |
1000 1000 |
1250 1250 |
1600 1600 |
| 220V DC31 DC33 DC35 |
100 80 100 |
125 100 125 |
160 125 160 |
200 160 200 |
250 200 250 |
400 315 400 |
630 500 630 |
1000 1000 |
1250 1250 |
1600 1600 |
| The power of electromotor P(kW) | ||||||||||
| 380V | 32 | 63 | 80 | 100 | 132 | 220 | 280 | |||
| Overloading capability | ||||||||||
| Rated short time endurance current lcw(kA Rms)0.1S/1.0S | 9/5 | 20/10 | 20/10 | 25/12 | 25/12 | 40/20 | 50/25 | 90/50 | 90/50 | 90/50 |
| Switch on breaking capability | ||||||||||
| Rated breaking capacity(A Rms)AC33 380V | 800 | 1000 | 1000 | 1600 | 1600 | 3200 | 3200 | 8000 | 8000 | 8000 |
| Rated switch on capability(A Rms)AC33 380V | 1000 | 1250 | 1250 | 2000 | 2000 | 4000 | 4000 | 10000 | 10000 | 10000 |
| Rated short cicuit switch on capability lcm(kA peak value) | 10 | 12 | 12 | 17 | 17 | 30 | 30 | 50 | 50 | 50 |
| Mechanism life (circulate times) | 100000 | 10000 | 10000 | 10000 | 10000 | 5500 | 5500 | 4000 | 4000 | 3000 |
| Electric life(circulatetimes) | ||||||||||
| COSφ=0.65AC33 | 2000 | 1000 | 1000 | 1000 | 1000 | 500 | 500 | 500 | 500 | 500 |
| Switch time | ||||||||||
| 1-0-11or 11-0-1(s) 1-0 or 11-0(s) |
1.0 0.5 |
1.0 0.6 |
1.0 0.6 |
1.1 0.7 |
1.1 0.7 |
1.2 0.8 |
1.2 0.8 |
1.2 0.8 |
1.2 0.8 |
1.2 0.8 |
| Electric control consume | ||||||||||
| Power supply voltage 24V(DC)(w) 220V(AC)(w) |
25 25 |
75 75 |
75 75 |
75 75 |
75 75 |
90 90 |
90 90 |
90 90 |
90 90 |
90 90 |
| Operating moment(Nm) | 1 | 19 | 19 | 26 | 26 | 39 | 39 | 39 | 226028 | |
| Weight(Kg)3P | 5.0 | 7.2 | 7.2 | 8 | 8 | 39 | 10 | 22 | 22 | 34 |
| Weight(Kg)4P | 5.2 | 7.5 | 7.5 | 9 | 9 | 10 | 11 | 28 | 28 | 40 |
Next Page: MBQ10 Automatic Transformer Switch
Keyword: MBQ5 Automatic Transformer Switch Automatic Transformer Switches