Location: Home Page >> Automatic Transformer Switch >> MBQ5 Automatic Transformer Switch

back
MBQ5 Automatic Transformer Switch

MBQ5 - Automatic Transformer Switch

 

Summarization:
MBQ5 automatic transfer switch(ATSE) is composed of switch and logic,and without additional controller.The faceplate showed with LCD and the operation be arranged by total English,it achieved the machine and power incorporately.It has the function of voltage text,frequency text,communication interface,fire fighting interface,electric,and inlock,and could achieve automatic,dynamoeletric long-distance,urgently manual control.
Operation been effected by the logic control board with kinds of logic order to manage the operation circulation of electromotor and gear-box.The electromotor drive the switch spring to cumulate the energy and release indtantaneously accelerating machine,connect the breaking circuit or the circuit transformation.It could achieve the safe insulation through obvious and eyeable estate enhance the all items of the electric capability and machine capability.
The whole switch are made of matel crust,cabinet and solid which is below 100A.The switch above of 125A whose crust is made of metal and the switch part adopts glass fibre unsaturalted polyester colophony hull,with strong insulating capability,protecting capability and reliable operating safety capability.
This switch is suitable for the automatic transfer of the main power supply and reverse power supply of the power supply system or the automatic transfer of the two pieces of the loading equipment and the safety insulation.
This switch has the advantage of handsome sculpt,new and compact design,small volumeand full function,it is the perfect choice among the congener products.
MBQ5 series products have passed the test of electromagnetism compatible capability and get the fullwill authentication certification.

According to the standard:
International standard:IEC60947-1(1998)(The first part of the low voltage switch equipment and control equipment:general principles)
State standard:GB/T 14048.1-2002(Low voltage switch equipment and control equipment:general principles)

The circumstance and the prupose for usage:
The circumstance for usage:
    The height above sea level is not exceed 2000 meters;
    The circumstance temperature is not higher than 40 and not lower than -5;
    The opposite humidity is not bigger than 95%;
    The circumstance without any medium of the danger f blast;
    The circumstance without any rain and snow affection.
    Note:If it used anticipatively under the condition of the circumstance temperature higher than +40 or below thann -5 to -45,the user should explain it to the manufacturer.
    Usage:Altemating current,50Hz,rated voltage 380V,direct current rated voltage 220V,rated current to 1600A.used for noncontinually switch on and breaking circuit.


Electric capability and mechanism capability:

Rated current(A) 16A 20A 25A 32A 40A 50A 63A 80A
Rated insulating voltage Ui(V) 500 500 500 500 500 500 500 500
The strength of insulating power (V) 3000 3000 3000 3000 3000 3000 3000 3000
Rated concussion endurance voltage Uimp kV(The installation sort IV) 6 6 6 6 6 6 6 6
Rated operating current le(A)                
380V AC31
         AC33
         AC35
16
16
16
20
20
20
25
20
25
32
25
32
40
32
40
50
40
50
63
40
63
80
63
80
220V DC31
         DC33
         DC35
16
16
16
20
20
20
25
20
25
32
25
32
40
32
40
50
40
50
63
40
63
80
63
80
The power of electromotor P(kW)                
380V 8 10 15 15 20 25 30 30
Overloading capability                
Rated short time endurance current lcw(kA Rms)0.1S/1.0S 9/5 9/5 9/5 9/5 9/5 9/5 9/5 9/5
Switch on breaking capability                
Rated breaking capacity(A Rms)AC33 380V 125 160 200 250 320 400 500 640
Rated switch on capability(A Rms)AC33 380V 160 200 250 320 400 500 630 800
Rated short cicuit switch on capability lcm(kA peak value) 8 8 8 8 8 8 10 10
Mechanism life (circulate times) 100000 100000 100000 100000 100000 100000 100000 100000
Electric life(circulatetimes)                
COSφ=0.65AC33 2000 2000 2000 2000 2000 2000 2000 2000
Switch time                
1-0-11or 11-0-1(s)
1-0 or 11-0(s)
1.0
0.5
1.0
0.5
1.0
0.5
1.0
0.5
1.0
0.5
1.0
0.5
1.0
0.5
1.0
0.5
Electric control consume                
Power supply voltage
24V(DC)(w)
220V(AC)(w)

25
25

25
25

25
25

25
25

25
25

25
25

25
25

25
25
Operating moment(Nm) 1 1 1 1 1 1 1 1
Weight(Kg)3P 4.8 4.8 4.8 4.8 4.8 4.8 4.8 5.0
Weight(Kg)4P 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.2

Rated current(A) 100A 125A 160A 200A 250A 400A 11630A 1000A 1250A 1600A
Rated insulating voltage Ui(V) 500 500 500 500 500 500 500 500 500 500
The strength of insulating power (V) 3000 5000 5000 5000 5000 8000 8000 1000 10000 10000
Rated concussion endurance voltage Uimp kV(The installation sort IV) 6 8 8 8 8 12 12 12 12 12
Rated operating current le(A)                    
380V AC31
         AC33
         AC35
100
80
100
125
125
125
160
160
160
200
200
200
250
250
250
400
340
400
630
536
630
1000

1000
1250

1250
1600

1600
220V DC31
         DC33
         DC35
100
80
100
125
100
125
160
125
160
200
160
200
250
200
250
400
315
400
630
500
630
1000

1000
1250

1250
1600

1600
The power of electromotor P(kW)                    
380V 32 63 80 100 132 220 280      
Overloading capability                    
Rated short time endurance current lcw(kA Rms)0.1S/1.0S 9/5 20/10 20/10 25/12 25/12 40/20 50/25 90/50 90/50 90/50
Switch on breaking capability                    
Rated breaking capacity(A Rms)AC33 380V 800 1000 1000 1600 1600 3200 3200 8000 8000 8000
Rated switch on capability(A Rms)AC33 380V 1000 1250 1250 2000 2000 4000 4000 10000 10000 10000
Rated short cicuit switch on capability lcm(kA peak value) 10 12 12 17 17 30 30 50 50 50
Mechanism life (circulate times) 100000 10000 10000 10000 10000 5500 5500 4000 4000 3000
Electric life(circulatetimes)                    
COSφ=0.65AC33 2000 1000 1000 1000 1000 500 500 500 500 500
Switch time    
 
         
 
 
1-0-11or 11-0-1(s)
1-0 or 11-0(s)
1.0
0.5
1.0
0.6
1.0
0.6
1.1
0.7
1.1
0.7
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
Electric control consume                    
Power supply voltage
24V(DC)(w)
220V(AC)(w)

25
25

75
75

75
75

75
75

75
75

90
90

90
90

90
90

90
90

90
90
Operating moment(Nm) 1 19 19 26 26   39 39 39 226028
Weight(Kg)3P 5.0 7.2 7.2 8 8 39 10 22 22 34
Weight(Kg)4P 5.2 7.5 7.5 9 9 10 11 28 28 40


back