MNLN6-63 RCBO

MNLN6-63 RCBO - Circuit Breaker

 

Sphere of application:
MNLN6-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage.
MNLN6-63 series leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short-circuited as well as infrequent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1.

Basic specification and main parameters:

Frame 63A
Rated working voltage 240V
Rated frequency 50/60Hz
Rated working current 2,3,3,6,16,20,25,32,40,50,63A
Rated residual operating current 0.01,0.03,0.1,0.3A
Rated residual un-operating current 0.005,0.015,0.05,0.15A
Sensibility A & ACType
Maximum operating time I△n t≤0.1s , 5I△n t≤0.04
Rated making and breaking capacity In≤50A 500A,In=63A 630A,In=63A 1500A
Instant release type B& C Type
Limiting value of un-operating current 6In
Rated limiting short-circuit current 10000A
Pole number 1P+N
Mechanical life 4000
Electric life 20000

The over-current tripping unit protection feature:
Frame 63A
Rated working voltage 240V
Rated frequency 50/60Hz
Rated working current 2,3,3,6,16,20,25,32,40,50,63A
Rated residual operating current 0.01,0.03,0.1,0.3A
Rated residual un-operating current 0.005,0.015,0.05,0.15A
Sensibility A & ACType
Maximum operating time I△n t≤0.1s , 5I△n t≤0.04
Rated making and breaking capacity In≤50A 500A,In=63A 630A,In=63A 1500A
Instant release type B& C Type
Limiting value of un-operating current 6In
Rated limiting short-circuit current 10000A
Pole number 1P+N
Mechanical life 4000
Electric life 20000

Model and meaning:
MNLN6-63 RCBO Meaning - Circuit Breaker
Operation principle:
MNLN6-63 RCBO Operation principle - Circuit Breaker
Dimensions(mm):
MNLN6-63 RCBO Dimensions - Circuit Breaker