MNLE1-32 Residual Current Circuit Breaker

MNLE1-32 Residual Current Circuit Breaker - Circuit Breaker

 

Sphere of application:
MNLE1-32 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, three phase 240/415V and below, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage. KNLE1-32 series leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short-circuited as well as infre- quent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1.

Basic specification and main parameters:

Frame class 32A
Rated working voltage 240/415V
Rated frequency 50/60Hz
Rated working current 16,20,25,32A
Rated residual operating current 0.03A
Rated residual un-operating current 0.015A
Sensibility AC Type
Maximum operating time I△n t≤0.1s , 5I△n t≤0.04
Instant release type C Type
Limiting value of un-operating current 6In
Rated limiting short-circuit current 4500A
Pole number 1P+N,2P,3P,3P+N
Mechanical life 8000
Electric life 4000

The over-current tripping unit protection feature:
Sequence NO . Release Test current I/In Start state Tripping time Expected restlt
1 c 1.13In Cold state t≤1h Not tripping
2 c 1.45In Start right after the serial NO.1 test t<1h Tripping
3 c 2.55In Cold state 1s<t<60s Tripping
4 c 5In Cold state t≤0.1s Not tripping
5 c 10In Cold state t<0.1s Tripping

Model and meaning:
MNLE1-32 Residual Current Circuit Breaker Meaning - Circuit Breaker
Characteristics curve:
MNLE1-32 Residual Current Circuit Breaker Characteristics curve - Circuit Breaker
Dimensions(mm):
MNLE1-32 Residual Current Circuit Breaker Dimensions - Circuit Breaker


back