QSA Isolating Switch Fuse

Applications:
Used to cabinet and drawer electrical controlling sets of equipment. Used as power switch isolating switch and emergency switch to protect circuit in distribution circuit and motor circuit, particularly the high-short circuit of AC 50-60Hz, the rated operational current 63-630A, rated operational voltage 660V below, current voltage 220V or 440V. Conformed to AC-21, AC-22, AC-23. It conforms to IEC60947-3.
Specifications:
| Model | QSA63 | QSA125 | QSA160 | QSA250 | QSA400 | QSA630 |
| Number of Main Poles | 2,3,4 | 2,3 | ||||
| Rated Insulation Voltage(V) | 1000 | |||||
| Rated Operational Voltage(V) | AC:380V 660V DC:220V 440V | |||||
| Rated Conventional Themal Current lth(A) | 80 | 160 | 160 | 400 | 400 | 800 |
| Rated Enclosed Thermal Current I the (A) | 63 | 125 | 160 | 250 | 400 | 630 |
| Rated Operational Current(le)/power AC | ||||||
| 380V cos0.35 AC23(A/KW) | 63/30 | 125/75 | 160/90 | 250/132 | 400/200 | 630/333 |
| 380V cos0.35 AC23(A/KW) | 63/55 | 125/110 | 160/150 | 250/220 | 400/375 | 630/560 |
| Rated Fused Short-Circuit Current(KA.m.s) | 100(380V) | |||||
| 50(660V) | ||||||
| Max. Fuse-Link(A) | 160 | 400 | 630 | |||
| Mechanical Endurance (Operations) | 15000 | 12000 | 3000 | |||
| Electrical Endurance (Operations) | 1000 | 300 | 200 | |||
| Weight (kg) | 1.6 | 1.7 | 4.1 | 4.5 | 4.7 | 14.0 |
| Fuse Type NT (RT16)(size) | 00 | 1-2 | 3 | |||
| Required Torque(Nm) | 7.5 | 16 | 60 | |||
| Auxiliary Switch(380V AC-15) (220VDC-13A) | 4 | 6 | ||||
| Switched Neutral Pole lth/le(220VDC-13A) | 63/63 | 125/125 | 160/160 | 250/250 | 400/400 | D |
| Neutral Link Lthe(A) | 63 | 125 | 160 | 250 | 400 | 630 |