Location: Home Page >> Circuit Breaker >> Miniature Circuit Breaker >> NC100H 2P Miniature Circuit Breaker

Specification
| Product Details | Manufacturer: Meba Electric Enterprises | ||
| Country of Origin: China | |||
| Brand: Meba | |||
| Model: NC100H | |||
| Manufacturing Standards | IEC60947 | ||
| Tropicalization | Relative Humidity | ![]() |
93% RH at 25![]() |
| Room Temperature | ![]() |
-5 a 40![]() |
|
| Electrical Properties | Rated at 40![]() |
A | 63/80/100/125 |
Rated operating voltage at 40 |
Vac | 240/415 | |
| Nominal Frequency | Hz | 50/60 | |
| Interrupting Capacity at 230V | kA | 10 | |
| Operating temperature | ![]() |
-5 a 40![]() |
|
| Degree of Protection | IP20 | ||
| Number of poles | 1/2/3/4 | ||
| Conductor cross section (minimum allowable) | mm2 | 63A/15 80A/25 100A/35 |
|
| Minimum number of power moves | 4000 | ||
| Minimum number of mechanical operations | 8000 | ||
| Operation curve | C/D | ||
| Current Trip Curve | A | Type C: 5 a 10 In Type D: 10 a 14 In |
|
| Characteristic Intervention | attach | ||
| Type Of Assembly | FOR RIEL DIN 35 mm | ||
| Operation Indicator Window | The circuit breaker have an operating window color display that shows the state in which it is (connected or disconnected). | ||
| Features | MAGNETIC COIL: ensures the switching of short-circuit, speaking within the following ranges: 5 to 10 times rated current (Type C), 10 to 14 times rated current (Type D) | ||
| BIMETAL: ensures the breaker trip when overloaded. | |||
| ARC CHAMBER: effectively dissipates the electric arc that is generated by the opening contacts of the trigger mechanism in the presence of an overload or short circuit. | |||
| Present Certificates | CE | ||
| ISO 9001-2000 awarded by the competent certification body, Meba is qualified in the manufacturing of the object | |||
| IEC 60898 standards in the manufacture of the goods | |||
| Curve compliance issued Shot by an accredited laboratory for effect | |||
| Life, given by Meba to ensure that the life of the goods offered by at least 15 years. | |||
| Testing For Acceptance | Before receiving the circuit breakers(breakers), customers may perform the tests may be necessary to ensure compliance with the technical specifications. | ||
| Packing | The packaging is sure that withstand any adverse conditions during transport and handling to the warehouse of cutomers. | ||
| Dial Century, Year, Month and Batch | In one of its sides the breaker is marked with permanent ink, year, month and batch. | ||
| Catalog | Attach catalogs indicating the technical specification | ||
| Shows | Submit sample of the product offered | ||
| Technical Warranty | 2 YEARS | ||
| Place of Delivery | CNF&FOB | ||
| Delivery | 25 DAYS | ||
The over-current protection property
| Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | NOte |
40 2![]() |
Cold position | 1.05In(In 63A) |
t 1h |
Non-release | - |
| Cold position | 1.05In (In 63A) |
t 2h |
Non-release | - | |
| Carried out immedi-ately after previous test | 1.30In(In 63A) |
t 1h |
Release | Current smoothlyrises to specified value within 5s | |
1.30In (In 63A) |
t 2h |
Release | |||
-5 +40![]() |
Cold position | 8.00In | t 0.2s |
Non-release | - |
| Cold position | 12.00In | t 0.2s |
Non-release | - |
Overall & Installation Dimensions





2
63A)
1h
63A)
+40