FAQs Contact Us Catalogue Download paypal
Location: Home Page >> Contactor >> AC Contactor >> MBC1-F AC Contactor

MBC1-F AC Contactor

MBC1-F AC Contactor, MBC1-F Magnetic Latching Contactor
MBC1-F Magnetic latching Contactor
Magnetic latching contactors of both block and bar mounted types are fitted with a special electromagnet which enables them to remain in the "On" position when the coil is no longer energized.

Applications
The special properties of magnetic latching contactors make them suitable for a large number of applications.
- Refineries, power stations, excitation circuits.
- Contactors remaining in the closed state for long periods. Examples: refineries, power supplies, low voltage distribution.
- Selective opening control.
- No unwanted opening and closing of the main power poles.
- Current carrying at voltages up to 1000 Volts.

Properties
- Retention of the sequence memory in automatic control equipment in the event of loss of control voltage.
- Energy saving, since the source of supply to the coil does not need to supply current when the contactor is latched in the closed state.
- Change of state from "Closed" to "Open" by current signal through the coil.
- Unaffected by mains interference.
- Utilisation of contactors beyond their breaking capacity, as operations are performed off-load.
- Contactors are silent in the latched position.

Operation of the electromagnet (GCR1-F block contactors)
- GCR1-F magnetic latching contactors are fitted with a double coil with 3 terminals comprising a latching winding and an unlatching winding. The 2 windings have a common point which can necessitate special wiring precautions when the latching supply is separate from the unlatching supply.
- The power supplies may be a.c. or d.c. For d.c. operation, the polarities indicated must be complied with.
- Operating precautions: the 2 windings must not be supplied simultaneously, a winding must not be supplied continuously, supply to the coils must be via pulsed contacts.
- Manual opening: if the control voltage is not present, the contactor can be unlatched manually.

Technical Data

Type MBC1-F115 MBC1-F150 MBC1-F185 MBC1-F225 MBC1-F265 MBC1-F330
Rated working current (A) AC-3 115 150 185 225 265 330
AC-1 200 250 275 315 350 400
Standard power ratings of 3-phase motors AC-3 (KW) 220/230V 30 40 55 63 75 100
380/400V 55 75 90 110 132 160
415V 59 80 100 110 140 180
440V 59 80 400 110 140 200
500V 75 90 110 129 160 200
660/690V 80 100 110 129 160 200
1000V 65 65 100 100 147 160

 

Type MBC1-F400 MBC1-F500 MBC1-F630 MBC1-F780 MBC1-F800
Rated working current (A) AC-3 400 500 630 780 800
AC-1 500 700 1000 1500 1500
Standard power ratings of 3-phase motors AC-3 (KW) 220/230V 110 147 200 220 220
380/400V 200 250 335 400 400
415V 200 280 375 125 420
440 250 295 400 425 420
500V 257 355 400 450 430
660/690V 280 335 450 475 470
1000V 185 335 450 450 450

Previous Page: LC1-K0910 AC Contactor